• Call Us: + 91-22-42555333
  • Contact Person : MR. Kamlesh Panchal
Get social with us!

Temperature and Relative Humidity Data Logger – HTL-804

Bar Graph Indicator Model BGI-144

Process Control Instruments

Temperature and Relative Humidity Data Logger – HTL-804

Product Description :

HTL-804 – 8 Channel T + RH Data logger with 2 common High / Low Alarm relay outputs + 16 independent relay drivers + Real time clock + Built in data storage + RS-485 serial interface or RS-232 for serial Dot-matrix printer.
HTL-804-U1 – Uses Rotronic make HYGROCLIP-XD sensors.
HTL-804-U2 – Uses Libratherm make HTS-440 sensors.
HTL-804-U3 – Uses Libratherm make HTS-220 sensors.
HTL-804-U4 – Uses any type of T+RH Transmitters giving 4-20mA signals.

Technical Specifications :

ParametersDescription
ParameterDescription
No. of channels8 nos. (4 Temperature + 4 %Rh)
Input type U10-1VDC proportional to Temperature and RH from Rotronic Hygroclip-XD
Input type U2Pt-100 + 0-3.3VDC proportional to Temperature and RH from HTS-440
Input type U3Pt-100 + 0-3.3VDC proportional to Temperature and RH from HTS-220
Input type U44-20mA proportional to Temperature and RH values - scalable
RangeFor Temperature -40 to 60 oC (U1) or -20 to 80oC (U2) OR 0 to 60oC (U3) For RH 0 to 100%.
AccuracyBetter than ± 0.3?C for temperature using class A Pt-100 element
Better than +/-1% (U1), Better than +/-3% RH (U2 and U3)
Display5 digit each 0.5" 7-segment Red /Green LED to indicate Temp and RH values,
Alarm values and Real Time Clock and 2 digit 0.3” 7-segment Red LED to display channel no.
Scan Rate1 to 99 sec (programmable through front panel keyboard)
Data Storage Interval1 to 99 minutes (user programmable).
Data Storage8000 records. (512KB).
Print Interval1 to 99 minutes (User programmable)
Skip/Hold FacilityAvailable through key board in configuration mode
High / Low AlarmCommon or individual Settable using key pad
Common Relay output2 nos. potential free change over contacts
(1 each for high and low output but common for all the channels)
Alarms Outputs (Optional)8 x 2 open collector outputs to drive external relay cards.
8 nos. for Temperature and 8 nos. for RH.
LED Indication8 x dual colour LEDs in the front indicating status of each alarm output.
Serial InterfaceRS-485 over MODBUS RTU protocol in the slave mode for PC interface or
RS-232 serial port for dot matrix printer interface
(any one is available at a time)
Supply90V - 260VAC VAC ± 10% (10VA), 50/60Hz or 24VDC/AC @ 200mA
EnclosurePlastic enclosure with polycarbonate front graphic.
Size of DATALOG-80496 x 96 x 160 mm.
Size of the Relay Card RLY-8190 L x 120 W x 75 D mm (35 mm DIN rail mount)
?